APPENDIX A -- USER INTERFACE MENUS (CON’T)
Field Assistant Menu
Access
Level
3=ADMIN
2=USER
1=No PW
POINT NAME BACnet Object RANGE DEFAULT
SERVICE TEST
Properties>
Control Program>
Configuration>
Service Configuration>
Service Test
Service Test test_enable Disable/Enable Disable
Fan Test fan_test Disable/Enable Disable
High Speed Fan Test hi_spd_test Disable/Enable Disable
Compressor 1 Test comp1_test Disable/Enable Disable
Compressor 2 Test comp2_test Disable/Enable Disable
Heat 1 Test heat1_test Disable/Enable Disable
Heat 2 Test heat2_test Disable/Enable Disable
Reversing Valve Test rev_vlv_test Disable/Enable Disable
Dehumidification Test dehum_test Disable/Enable Disable
Power Exhaust Test pexh_test Disable/Enable Disable
Economizer Test econ_test 0-100 %Open 0
VFD Speed Test vfd_spd_test 0-100% 0
UNIT MAINTENANCE
Properties>
Control Program Maintenance>
Unit
3 Occupancy Status occ_status Occupied/Unoccupied
N/A Temp Compensated Start
-Or-
Learning Adaptive Start
tcs_status
-Or-
aos_status
Inactive/Active
3 Pre Occupancy Purge purge Inactive/Active
N/A Space Temp Sensor spt_status 1=Sensor Failure
2=SPT Sensor
3=T55/T56
4=Network
5=Airside Linkage
6=Locked Value
3 Effective Heat Setpoint effective_ht_stpt 0-120°F
3 Effective Cool Setpoint effective_ci_stpt 0-120°F
N/A Relative Humidity Source rh_source 1=N/A
2=Local
3=Network
4=Linkage
5=Locked Value
6=Linkage&Local
N/A IAQ Source iaq_source 1=N/A
2=Local
3=Network
4=Linkage
5=Locked Value
6=Linkage&Local
N/A OAQ Source oaq_source 1=N/A
2=Local
3=Network
4=Linkage
5=Locked Value
6=Linkage&Local
N/A Outdoor Air Temperature Source oat_status 1=N/A
2=Local
3=Network
4=Linkage
5=Locked Value
N/A System Status
N/A Safety Chain Feedback safety_status Off/Run Enabled
N/A Fire Shutdown Status firedown_status Run Enabled/Shutdown
N/A Compressor Safety Status comp_status Normal/Trouble
N/A Calculated Min Econ Pos cal_min_econ_pos 0-100%
N/A Calculated PE Setpoint cal_pe_stpt 0-100%
3 Active Compressor Stages comp_run 0-2
3 Active Heat Stages heat_run 0-2
N/A Enthalpy Status enthalpy_status High/Low
N/A Enthalpy BACnet oae High/Low
N/A Humidistat Input Status humstat_status High/Low
N/A Filter Status filter_status Clean/Dirty
N/A Door Contact Status door_contact_status Off/On
3 Reset Supply Fan Runtime Alarm sfan_rntm_clr Run/Clear Run
N/A Reset Comp 1 Runtime Alarm comp1_rntm_clr Run/Clear Run
N/A Reset Comp 2 Runtime Alarm comp2_rntm_clr Run/Clear Run
3 Reset Filter Runtime Alarm filter_rntm_clr Off/On Off