DESCRIPTIONAll 588A models feature one piece, compact design and are fullyself-contained units that are prewired, prepiped, and pre-charged for minimu
DIMENSIONAL DRAWINGS (cont)Manual Outdoor-Air DamperFilter Racks and FiltersACCESSORY PART NUMBER ‘‘A’’FILTERRACKCPFILTRK001A00 2111⁄169CPFILTRK002A00
SPECIFICATIONSUNIT SIZE 588A 018040 024040 024060 030040 030060 030080NOMINAL CAPACITY (tons) 11⁄22221⁄221⁄221⁄2OPERATING WEIGHT (lb)Without Base Rail
SPECIFICATIONS (cont)UNIT SIZE 588A 042100 042120 048080 048100 048120 048140NOMINAL CAPACITY (tons) 31⁄231⁄24444OPERATING WEIGHT (lb)Without Base Rai
SELECTION PROCEDUREI DETERMINE COOLING AND HEATING REQUIRE-MENTS AT DESIGN CONDITIONS:Given:Required Cooling Capacity (TC) ...34,000 BtuhSensib
NET COOLING CAPACITIES588A018 (11⁄2TONS)IndoorCoil AirOutdoor Coil Entering-Air Temperature (F)85 95 105 115Cfm BFEwb(F)Capacity(Btuh x 1000)TotalSyst
NET COOLING CAPACITIES (cont)588A036 (3 TONS)IndoorCoil AirOutdoor Coil Entering-Air Temperature (F)85 95 105 115Cfm BFEwb(F)Capacity(Btuh x 1000)Tota
NET COOLING CAPACITIES (cont)588A060 (5 TONS)IndoorCoil AirOutdoor Coil Entering-Air Temperature (F)85 95 105 115Cfm BFEwb(F)Capacity(Btuh x 1000)Tota
DRY COIL AIR DELIVERY* — HORIZONTAL DISCHARGE(Deduct 10% for 208 v)UNITSIZE588AMOTORSPEED230 AND 460 VOLT HORIZONTAL DISCHARGEExternal Static Pressure
DRY COIL AIR DELIVERY* — VERTICAL DISCHARGE(Deduct 10% for 208 v)UNITSIZE588AMOTORSPEED230 AND 460 VOLT VERTICAL DISCHARGEExternal Static Pressure (in
WET COIL PRESSURE DROPUNIT SIZE588AAIRFLOW(cfm)PRESSURE DROP(in. wg)018600 0.069700 0.082800 0.102900 0.116024600 0.039700 0.058800 0.075900 0.0880309
STANDARD FEATURES (cont)LOW AND HIGH VOLTAGE ELECTRICAL ENTRIES allow lowand high voltage to be brought in either through the duct panelor rear flue pa
ELECTRICAL DATAUNIT588AV-PH-HzVOLTAGERANGECOMPRESSORCOND.FANMOTORINDOORFANPOWER SUPPLYAWG60CMIN WIRESIZEMAX WIRELENGTH(ft)Min Max RLA LRA FLA FLA MCA
OPERATING SEQUENCEHEATINGOn a call for heating, terminal ‘‘W’’ of the thermostat is ener-gized, starting the induced-draft motor. When the hall-effect
LEGENDAWG — American Wire GageBR — Blower RelayC—ContactorCAP — CapacitorCH — Crankcase HeaterCOMP — Compressor MotorCR — Combustion RelayEQUIP — Equi
LEGENDAWG — American Wire GageBR — Blower RelayC—ContactorCAP — CapacitorCH — Crankcase HeaterCOMP — Compressor MotorCR — Combustion RelayEQUIP — Equi
LEGENDAWG — American Wire GageBR — Blower RelayC—ContactorCAP — CapacitorCH — Crankcase HeaterCOMP — Compressor MotorCR — Combustion RelayEQUIP — Equi
TYPICAL INSTALLATIONPower WiringControl WiringOutdoor AirflowIndoor AirflowNEC — National Electrical CodeHorizontal DischargeCEILINGSUPPLY-AIRFLEXIBLE D
APPLICATION DATA1. Condensate trap — A 2-in. condensate trap must be fieldsupplied.2. Ductwork — Secure downflow discharge ductwork to roofcurb. For hor
BryantAir ConditioningCopyright 1997 Carrier CorporationSPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICEUNIT MUST BE INSTALLED IN ACCORDANCEWITH INSTAL
FIELD-INSTALLED ACCESSORY DESCRIPTION ANDUSAGE (cont)Lifting Bracket Kit — Provides attachment point for riggingstraps.SUGGESTED USE:• When unit needs
ARI* COOLING CAPACITIESUNIT 588ANOMINAL STANDARD NET COOLING†SEER†**SOUND RATINGS††TONS CFM CAPACITIES (Btuh) (Bels)018 11⁄2600 17,000 10.0 7.4024 2 8
DIMENSIONAL DRAWINGSUNITFin./mmGin./mmCENTER OF GRAVITY in./mmXYZ588A018040169⁄16/420.7 1815⁄16/481.025.07/637 20.59/52310.85/276588A024040 27.07/688
DIMENSIONAL DRAWINGS (cont)UNITFin./mmGin./mmCENTER OF GRAVITY in./mmXYZ588A018040197⁄8/504.8 221⁄4/565.425.04/636 22.72/57713.16/334.3588A024040 26.9
DIMENSIONAL DRAWINGS (cont)REQ’D CLEARANCES FOR SERVICING. in. (mm)Duct panel...0Unit top ...
DIMENSIONAL DRAWINGS (cont)REQ’D CLEARANCES FOR SERVICING. in. (mm)Duct panel...0Unit top ...
DIMENSIONAL DRAWINGS (cont)UNIT PART NUMBER ‘‘A’’588ACPRFCURB001A00 89 [203]CPRFCURB002A00 119 [279]CPRFCURB003A00 149 [356]NOTES:1. Roof curb must be