Rh terminal. Connect R from the outdoor unit to the Rc terminal. Then, break
jumper on the circuit board. The W and G signals are taken from the Rh power
and the Y and O signals are taken from the Rc power. If thermostat has been
installed in a two--transformer application that is later changed to a
single--transformer installation, installer must install a field supplied jumper
between Rc and Rh. Depending on the installation, up to 14 wires may be
required. Installation as two-- piece unit is recommended. Only 2 wires are
required for connection between Display Module and Equipment Control
Module.
A07052
Fig. 1 -- PCB Breakout Jumper
Models
There are programmable and non --programmable models for all applications.
They can be configured for AC or HP, 1--or 2--speed compressor, and for Hybrid
Heatt installations, allowing it to be used in place of all Bryant thermostats.
Programmable thermostats may be configured as non--programmable if user
desires.